Sdge 24v Trasformer Blows Again on the High Voltage Side Sdge Surges ?
Search FAQs
{"searchBar":{"inputPlaceholder":"Search past keyword or ask a question","searchBtn":"Search","error":"Please enter a keyword to search"}}
External Fusing Modify for 24vdc Momentum I/O Modules
Issue
The purpose of this Resolution is to inform users of 24vdc Momentum I/O Bases that the fusing requirement has changed.
Using a 315ma fast blow fuse on a redesigned 24vdc Momentum base may cause the fuse to blow when powered upward. Since the 24vdc Momentum I/O bases have been redesigned to encounter the new EMC and power hold-upwardly requirements, it was necessary to increase the size of the external fusing.
The external fusing is indicated in the User Manuals as follows. It does non bear upon the recommended fusing for the I/O power.
Product Line
Momentum
Environment
Resolution The 1A Dull Blow fuse can be used on both new and onetime versions of 24vdc powered Momentum I/O bases listed below. DC Discrete Modules
The recommended size of the external fuse for all Momentum I/O modules that are powered by 24 VDC, has changed from a 315ma Fast Blow fuse to a 1Amp Tedious Blow fuse (Bussmann GDC-1A or equivalent).
- 170ADI34000 24V DC - xvi Pt Input Module Base
170ADI34000C 24V DC - 16 Pt Input Module Base Coated
170ADI35000 24V DC - 32 Pt Input Module Base
170ADI35000C 24V DC - 32 Pt Input Module Base -Coated
170ADM35010 24V DC - 16 Pt Input/ xvi Pt Output Module Base of operations
170ADM35010C 24V DC - xvi Pt Input/ 16 Pt Output Module Base Coated
170ADM35011 24V DC - 16 Pt Input/ 16 Pt Output - Fast Response Module Base
170ADM35015 24V DC - 16 Pt Input/ 16 Pt Output Module Base - True Low Signals
170ADM39010 24V DC - xvi Pt Input/ 12 Pt Output - Monitored Module Base of operations
170ADM39030 24V DC - x Pt Input/ 8 Pt Relay Output Module Base
170ADM39030C 24V DC - 10 Pt Input/ 8 Pt Relay Output Module Base Coated
170ADO34000 24V DC - 16 Pt Output Module Base
170ADO34000C 24V DC - 16 Pt Output Module Base Coated
170ADO35000 24V DC - 32 Pt Output Module Base
170ADO35000C 24V DC - 32 Pt Output Module Base Coated
170ADM85010 x to 60 V DC - xvi Pt Input/ 16 Pt Output Module Base of operations
Analog Modules
- 170AAI03000 Analog - 8 Ch Differential Input Module Base
170AAI03000C Analog - eight Ch Differential Input Module Base Coated
170AAI14000 Analog - 16 Ch Single-Ended Input Module Base of operations
170AAI14000C Analog - sixteen Ch Single-Ended Input Module Base Coated
170AAI52040 Analog - 4 Ch RTD, Thermocouple, and Mv Input Module Base
170AAI52040C Analog - 4 Ch RTD, Thermocouple, and Mv Input Module Base Coated
170AAO12000 Analog - 4 Ch Output 0-20mA Module Base
170AAO92100 Analog - iv Ch Output 4-20mA Module Base
170AAO92100C Analog - 4 Ch Output 4-20mA Module Base Coated
170AMM09000 Analog - 4 Ch In/ 2 Ch Out Module Base, w/ 24V DC iv In/2 Out Digital
170AMM09000C Analog - 4 Ch In/ 2 Ch Out Module Base, w/ 24V DC four In/2 Out Digital Coated
170AMM09001 Analog - 4 Ch In/ ii Ch Out Module Base, westward/ 12V DC 4 In/2 Out Digital
Specialty Modules
- 170AEC92000 High Speed Counter Module Base of operations
{"support":{"yesButton":"Yes","noButton":"No","feedback":{"title":"What can we do to improve?"},"submitButton":"Submit","successMessage":"Thank you for your feedback","title":"Was this helpful?","feedbackPercentLabel":"of people institute this helpful","captcha":{"mistake":"Please check the box"}}}
Source: https://www.se.com/us/en/faqs/FA198167/